Friday, May 17, 2019

How temperature switch works?



Temperature sensor is a device, to measure the temperature through an electrical signal it requires a thermocouple or RTD (Resistance Temperature Detectors). The thermocouple is prepared by two dissimilar metals which generate the electrical voltage indirectly proportional to change the temperature.

Friday, August 29, 2008

Turbine Drain Sump Pit - Upgrading Level Probe Switch to Ultrasonic Switch Type

Project in Progress - Turbine Drain Sump Pit - Upgrading Level Probe Switch to Ultrasonic Switch Type

The previous level probe switch always giving fault signal and disturbs controlling of the water level in the system. The new type of Ultrasonic Model non-contact which expected to be more robust and reliable.

Specifications:

FDU91F-RN1A* PROSONIC S
FMU90-R11CA131AA1A* PROSONIC S

RSG30-A1A1AAA1* ECOGRAGH T

Now it is almost complete.



Monday, August 25, 2008

Kelco F25-B Series Corrosive Flow Switch

Kelco F25-B Series Corrosive Flow Switch

This is a new flow switch that we found at market and currently installed at our electrolyser ECP Stream. Alternative to Flotech ECP Flow Switch which give a lot of problems recently.

Anyway, just for your information this kind of switch already used 3 months and the result is very good and no defect from operation at all so far. If this F25-B Series Corrosive Flow Switch can be long lasting live, I would consider this one to replace the old Flotech brand flow switch. At least maybe 1 year... mmmm... what do you think?

Kelco F25-B Series Corrosive Flow Switch at Pipe

Full Specifications are as follow:

F25 SERIES CORROSIVE
RESISTANT FLOW SWITCH
BRAND : KELCO, MODEL : F25-B
DRY RED SWITCH, 240V AC 200V DC 1A

Anyone has use this product before? Please shares here. Thanks...


Tuesday, July 15, 2008

Differential Pressure Switch Pyropress SDP1502 /B710A30/SM5X



Brand: Pyropress
Model No: SDP1502 /B710A30/SM5X
Working Pressure: 0.1 to 1.7 Bar

We are looking this DP Switch to replace the defective instrumentations.

Monday, April 14, 2008

FLOW SWITCH WE ANDERSON FLOWTECH V8 A09P

ITEM: FLOW SWITCH FLOWTECH
MODEL : V8 A09P
MAKER: W.E.
ANDERSON
LENGTH OF FLAP: 80MM
POWER SUPPLY: 125/250 VAC, 5 AMP

OUTPUT: 4-20 mA, 2
WIRE

Quantity: 50 Pieces urgently required because the stock is running currently low.



Thursday, April 10, 2008

United Electric Controls UE DP Switch J120K-157- M210

United Electric Controls UE DP Switch J120K-157- M210

I'm trying to check whether this is correct UE DP Switch that we need to purchase or not. Anyway just posting out and share with you. More details you can check schematic diagram or drawing here.

Wednesday, March 19, 2008

Inductive Sensor IC5005 ICE3040-FPKG IFM Electronics

This inductive sensor or limit switch currently used at the Fly Ash Silo Cone Closing System to give signal open/close to PLC for ash to disharge to the tanker.

Tuesday, March 11, 2008

Thermo Ramsey Granuflow Detector GTR 130

The Thermo Ramsey Granuflow non-contact flow sensor ideally for monitoring flow in pipeline, ducts, air-slides, and at transfer points of vibrating chutes, conveyor belts and bucket elevators. Currently used at the SO3 Injection System (Boiler Side) in our coal fired power plant to monitor sulfur dosing.

Thermo Ramsey Granuflow Detector GTR 130

The GTR 130 sensor has no moving mechanical parts. This eliminates wear of the sensor and makes the instrument maintenance and trouble-free.

Details Specification:

Description
: Flow Switch
System : SO3 Injection System (Boiler Side)
Model : Granuflow GTR 130
Maker : Thermo Ramsey
Input volatage : 20-30 V AC/DC Relay contact (NO)
Rating max: 250 V 4A


Friday, February 15, 2008

Trial Instrumentation Field Device ECP Flow Switch Chlorine Application Failed

Again, this morning operation raised defect to us on Electro Chlorination Plant (ECP) flow switch problem. After a few days switch has been installed with minor modification on the probe; new spring changed to stainless steel and the flapper is coated with anti-oxide hoping that the lifetime can be longer than before, but the result frustrated. There is already a few times I mentioned in this blog that the unreliable flow switch urgently needs to be replaced as the ECP Cell downtime very frequently happened.

Recently, Vega and Endress Hauser tested their probes on the ultrasonic type. It took one week to complete in January. The tuning of the parameters has been done for a few times to get a good result but at the last stage it failed. The reason it failed is the flow rate is not stable due to two medium mixture, water and air bubbles. In this case, air bubbles will absorb the signal from the ultrasonic then cause the reading fluctuating. At the end, they would like to trial another type of measurement either magnetic or different pressure DP type. But I am still waiting for them to their recommendation which has been promised in February.

I still remember that the current Flotech flow switch that we are using already more than two years. But recently in these 3 to 4 months, the flow switch flapper and the spring brittles and easily broken. Actually this is not the first time we change to a new brand on ECP flow switch. If I am not mistaken, it is already third or fourth times since 2004. So far most of our instrumentation field devices when comes to a new solution doesn’t give us much trouble. Aaarrrgghh… meaning that I have to find out other new brand or new type of flow switch to cut this problem from happens and happens again.

At this moment, I have to contact various manufacturers to recommend the suitable flow switch on the chlorine application which urgently required including ABB, UE and Kelco. Since the stocks balances at the store for the old type (Flotech) are very critical low therefore we need to reorder for temporary used.

Monday, January 21, 2008

ECP Flow Switch Already Delivered Today

If you remember my previous post about this flow switch, the stock already zero at our store. At the moment the ECP Flowtech flow switch give a lot of problem to us.

10 New Pieces ECP Flowtech Flow Switch Delivery in a Box

The root cause of the problem it is always broken or the spring easily drop off because of the chlorine which we know that it's create corrosion. We got 10 pieces. Anyway need to modify to 2.5 inch and put some weightage at the end of the rod. The project to change to the new non-contact sensor still in progress. Will update later.

WTP ACID DAY TANK LEVEL MAGNETIC SWITCH FAULTY

Acid Day Tank Level Magnetic Switch faulty today as per photo below. Need to replace with the new. Try to get the original specification from the switch itself but nothing was found. Except it's brand Jola.


Need to get a new brand from local supplier and easy to purchase. Anyway, we still have three spares at the store before everything finish and have the time to manage.

Saturday, January 19, 2008

Washdown Water Sump Level Switch

Washdown Water Sump Level Switch
09ETK90CL010 & CL011 TT4

Defect – Operator called to check Low Level Alarm cannot be reset and High Level Alarm not activate. This will caused pump can’t cut in to pump water from drain pit. The reason to drain water is to allow mechanical team clear sludge from pit.

Check at local simulate both signal for Low and High Level for pump cut in. After all water cleared normalize back simulation. Inform operator to monitor again water level after mechanical team clear the sludge.

Monday, January 7, 2008

Electrochlorination Plant (ECP) Flow Switch

Called by operation to check ECP no.1 flow switch failed at stream A. From operation feedback, ECP No 1 tripped on no flow on stream A. Operation tried putting ECP No 1 in service early morning today. It could be the following:-

1. Flow switch faulty. Based on our discussion our instrument team (C&I) worked on the flow switch last Saturday.

2. Actual no flow due to wrong isolation, clogging of the inlet pipe, clogging of the outlet pipe.

Permit issued and found switch spring disconnected. Repair the spring and fixing back the switch. Waiting operation to test run. Currently we are lack of this flow switch type and need to reorder. The specification and the photo as below:

Electrochlorination Plant (ECP) Flow Switch

Flotech Flow switch
Model = V8
Supply :125/250 VAC , 5 A
Manufacturer : Dwyer Intruments INC.
Michigan City, Indiana, USA