Friday, September 5, 2008
Cerabar S PMP75 - E+H Level Transmitter Installation
Tuesday, September 2, 2008
Cerabar S PMP75 - PMP75-ABA1HB8B3AAA CERABAR S DIGITAL PRESSURE TRANSMITTER
| Cerabar S PMP75 |
| Cerabar S with metallic measuring diaphragm and diaphragm seal. Overload-resistant and function-monitored. Communication via HART, PROFIBUS PA or FOUNDATION Fieldbus. Areas of application |
The Cerabar S pressure transmitter is used for the following measuring tasks:
| Absolute pressure and gauge pressure in gases, steams or liquids in all areas of process engineering and process measurement technology | |
| Level, volume or mass measurement in liquids | |
| HIgh process temperature with diaphragm seals up to 350°C (662°F) | |
| High pressure up to 700 bar This device we replace at the Druck 1830 Level Pressure Sensor Electro Chlorination Plant. In next post, I will enlosed together with the photos during the level sensor installation. More details about this level sensor transmitter: Click here Endress Hauser. |
Monday, August 25, 2008
Kelco F25-B Series Corrosive Flow Switch
Kelco F25-B Series Corrosive Flow SwitchAnyway, just for your information this kind of switch already used 3 months and the result is very good and no defect from operation at all so far. If this F25-B Series Corrosive Flow Switch can be long lasting live, I would consider this one to replace the old Flotech brand flow switch. At least maybe 1 year... mmmm... what do you think?
Full Specifications are as follow:
F25 SERIES CORROSIVE
RESISTANT FLOW SWITCH
BRAND : KELCO, MODEL : F25-B
DRY RED SWITCH, 240V AC 200V DC 1A
Anyone has use this product before? Please shares here. Thanks...
Sunday, August 17, 2008
Crowcon Hydrogen Leakage Detector Monitoring System - Flamgard Exe
Hydrogen is highly explosive gas. All of the 7 Hydrogen detectors in our Electro Chlorination Plant (ECP) are using Crowcon Hydrogen monitoring system.
A situation lead to an extremely dangerous explosive condition if one of the ECP streams were to develop a leak and Hydrogen concentration in the building reached above the Lower Explosive Limit (LEL).
Recommended Action when the alarm appeared:
- Troubleshoot the reason why the detectors give an alarm. If the detectors are functioning correctly, there should not be any spurious alarms. There would not normally be Hydrogen present in sufficient quantities.
- Zero the detectors using compressed air and calibrate using a suitable Hydrogen calibration gas.
- Uninhibit the Hydrogen detection input channels and restore the system to normal operation.
Saturday, August 16, 2008
Endress+Hauser Electromagnetic Flowmeter Promag 53 Project Update
Friday, August 15, 2008
Endress+Hauser Electromagnetic Flowmeter Promag 53
This situasion leads to several trial units of many brands to avoid this happen and happen again. Anyway, this one also a trial unit and if the result success will be considered.
Monday, April 14, 2008
FLOW SWITCH WE ANDERSON FLOWTECH V8 A09P
ITEM:
MODEL : V8 A09P
MAKER: W.E.
LENGTH OF FLAP: 80MM
POWER SUPPLY: 125/250 VAC, 5 AMP
OUTPUT: 4-20 mA, 2
Sunday, March 23, 2008
Druck 1830 Level Pressure Sensor at The Sodium Hypochloride Tank
I am not so sure about the specification and I will try find it later. So don't forget to come back to know more about this transducer.
Friday, March 21, 2008
Installation of Thermo Fisher SX40 at the Electrochlorination Plant
Related Articles you may read;
- Trial Instrumentation Field Device at ECP Failed
- ECP Flow Switch Delivered Today
- New Project Flow Switch at ECP
- Electrochlorination Plant Flow Switch
Sunday, March 16, 2008
Thermo Fisher Scientific SX40
"The Polysonics SX40 is a dedicated Doppler flowmeter which utilizes a patented digital signal processing technique to determine the flow of liquids that contain particulate or air bubbles. The meter incorporates clamp-on sensors which are easily installed for sludge management in sewage treatment plants and industrial applications such as slurry and effluent monitoring."Product details:
"The Hydra SX40 is designed as a permanently installed flow meter. Its large backlit graphics display provides excellent visibility even in poorly lit environments. As well as flow rate and flow total, a flow trend is available to quickly analyze flow over a period of time. This is especially useful for analyzing pump cycling activity. Standard outputs include 4-20mA, RS232 serial interface and up to four programmable relays. The flow meter also incorporates a 90,000-point data logger."
Friday, February 15, 2008
Trial Instrumentation Field Device ECP Flow Switch Chlorine Application Failed
Again, this morning operation raised defect to us on Electro Chlorination Plant (ECP) flow switch problem. After a few days switch has been installed with minor modification on the probe; new spring changed to stainless steel and the flapper is coated with anti-oxide hoping that the lifetime can be longer than before, but the result frustrated. There is already a few times I mentioned in this blog that the unreliable flow switch urgently needs to be replaced as the ECP Cell downtime very frequently happened.
Recently, Vega and Endress Hauser tested their probes on the ultrasonic type. It took one week to complete in January. The tuning of the parameters has been done for a few times to get a good result but at the last stage it failed. The reason it failed is the flow rate is not stable due to two medium mixture, water and air bubbles. In this case, air bubbles will absorb the signal from the ultrasonic then cause the reading fluctuating. At the end, they would like to trial another type of measurement either magnetic or different pressure DP type. But I am still waiting for them to their recommendation which has been promised in February.
Monday, January 21, 2008
ECP Flow Switch Already Delivered Today
Saturday, January 19, 2008
New Project Flow Switch at Electrochlorination Plant








There are two vendors promoting their product for testing, Vega and Endress Hauser. Both already installed their products and the testing result will be after 1 months installation.
Monday, January 7, 2008
Electrochlorination Plant (ECP) Flow Switch
1. Flow switch faulty. Based on our discussion our instrument team (C&I) worked on the flow switch last Saturday.
Permit issued and found switch spring disconnected. Repair the spring and fixing back the switch. Waiting operation to test run. Currently we are lack of this flow switch type and need to reorder. The specification and the photo as below:
Electrochlorination Plant (ECP) Flow Switch
Flotech Flow switch
Model = V8
Supply :125/250 VAC , 5 A
Manufacturer : Dwyer Intruments INC.